ANSUL FIRE PROTECTION, WORMALD U.S.INC. -- HALON 1301, FREON FE 1301 -- 6830-01-120-2711
===================== Product Identification =====================
Product ID:HALON 1301, FREON FE 1301
MSDS Date:01/12/1996
FSC:6830
NIIN:01-120-2711
MSDS Number: BYFZT
=== Responsible Party ===
Company Name:ANSUL FIRE PROTECTION, WORMALD U.S.INC.
Address:ONE STANTON STREET
City:MARINETTE
State:WI
ZIP:54143-2542
Country:US
Info Phone Num:715-735-7411...FAX 715-732-3477
Emergency Phone Num:715-735-7411...TOM LAWSON EXT 580
CAGE:03670
=== Contractor Identification ===
Company Name:ANSUL INC
Address:ONE STANTON STREET
Box:City:MARINETTE
State:WI
ZIP:54143-2542
Country:US
Phone:715-735-7411
CAGE:03670
============= Composition/Information on Ingredients =============
Ingred Name:TRIFLUOROBROMOMETHANE (HALON 1301) (SARA 313) (CERCLA)
CAS:75-63-8
RTECS #:PA5425000
Fraction by Wt: >99%
OSHA PEL:1000 PPM
ACGIH TLV:1000 PPM; 9495
Ozone Depleting Chemical:1
===================== Hazards Identification =====================
LD50 LC50 Mixture:LC50 (RAT) = >800,000 PPM/4 HOURS
Routes of Entry: Inhalation:YES Skin:YES Ingestion:NO
Reports of Carcinogenicity:NTP:NO IARC:NO OSHA:NO
Explanation of Carcinogenicity:MFR GAVE THE ABOVE LISTINGS ON THE MSDS
BUT NO OTHER COMMENTS WERE RECORDED ON THE MSDS.
Effects of Overexposure:DIZZINESS, IMPAIRED COORDINATION, REDUCED
MENTAL ACUITY, & CARDIAC EFFECTS CAN OCCUR. UNCONSCIOUSNESS OR
DEATH IN HIGH CONCENTRATIONS & LONGER EXPOSURES. NONE CHRONIC
EFFECTS KNOWN WHEN OCCUPATIONAL E XPOSURES ARE BELOW THE TLV.
Medical Cond Aggravated by Exposure:CARDIAC PROBLEMS.
======================= First Aid Measures =======================
First Aid:EYE:FLUSH WITH PLENTY OF WATER FOR 15 MIN WHILE HOLDING LIDS
OPEN. SKIN:WASH WITH COPIOUS AMOUNTS OF SOAP & WATER FOR AT LEAST
15 MIN, IF REDNESS, ITCHING OCCURS, GET MEDICAL ATTN. TREAT
FROSTBITE IF NECESSARY. INHALED:REMOVE TO FRESH AIR,IF COUGH OR
OTHER RESPIRATORY SYMPTOMS OCCUR, CONSULT MEDICAL PERSONNEL.
INGESTION:NOT LIKELY TO OCCUR.
===================== Fire Fighting Measures =====================
Flash Point:NON-FLAMMABLE
Extinguishing Media:THIS IS A FIRE EXTINGUISHING AGENT.
Fire Fighting Procedures:USE WATER TO COOL FIRE-EXPOSED CYLINDERS OR
OTHER CONTAINERS. USE SELF-CONTAINED BREATHING APPARATUS WITH FULL
FACEPIECE AND PROTECTIVE CLOTHING FOR FIRES.
Unusual Fire/Explosion Hazard:CONTAINERS ARE EQUIPPED WITH PRESSURE AND
TEMPERATURE RELIEF DEVICES, BUT RUPTURE MAY OCCUR UNDER FIRE
CONDITIONS AND TOXIC DECOMPOSITION BY-PRODUCTS CAN FORM.
================== Accidental Release Measures ==================
Spill Release Procedures:EVACUATE AREA. VENTILATE TO OUTSIDE
ATMOSPHERE. COOL OR REMOVE HOT, METAL SURFACES OR SOURCE OF
NON-EXTINGUISHED FLAMES.
Neutralizing Agent:MFR GAVE NO INFORMATION ON MSDS.
====================== Handling and Storage ======================
Handling and Storage Precautions:STORE AS A LIQUEFIED COMPRESSED GAS IN
DOT APPROVED PRESSURE VESSELS AWAY FROM HIGH TEMPERATURE. CYLINDER
MUST BE CAPPED OR CONNECTED FO A SYSTEM.
Other Precautions:NOTE INCOMPATIBILITY INFORMATION.
============= Exposure Controls/Personal Protection =============
Respiratory Protection:NOT NORMALLY NECESSARY IF CONTROLS ARE ADEQUATE.
FOR HIGH CONCENTRATIONS EXCEEDING 10% OR IF EXPOSURE IS PROLONGED,
USE POSITIVE PRESSURE AIR-SUPPLIED RESPIRATOR.
Ventilation:MECHANICAL RECOMMENDED IN LOW AREAS OR INDOORS WHERE VAPORS
MAY COLLECT. USE LOCAL EXHAUST TO CONTROL EXPOSURES.
Protective Gloves:PLASTIC IF WORKING W/LIQUID.
Eye Protection:CHEMICAL GOGGLES, FACE SHIELD
Other Protective Equipment:SAFETY SHOWER & EYE BATH IN WORK AREAS.
Work Hygienic Practices:MFR GAVE NO INFORMATION ON MSDS.
Supplemental Safety and Health
NONE
================== Physical/Chemical Properties ==================
HCC:G3
NRC/State Lic Num:NONE
Boiling Pt:B.P. Text:-72F,-58C
Vapor Pres:199 PSI
Vapor Density:5.2
Spec Gravity:1.57
Solubility in Water:NEGLIGIBLE
Appearance and Odor:COLORLESS GAS, SWEET ODOR
Percent Volatiles by Volume:100
================= Stability and Reactivity Data =================
Stability Indicator/Materials to Avoid:YES
ACTIVE METALS, FIRES OF METAL HYDRIDES.
Stability Condition to Avoid:DECOMPOSEEUNDER FIRE CONDITIONS ABOVE
900F.
Hazardous Decomposition Products:THERMAL DECOMPOSITION >900F FORMS
HYDROGEN FLUORIDE & HYDROGEN BROMIDE.
Conditions to Avoid Polymerization:WILL NOT OCCUR.
==================== Disposal Considerations ====================
Waste Disposal Methods:DISPOSE OF I/A/W FEDERAL, STATE & LOCAL
REGULATIONS.
Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.